Remote Reset
Description: The CMCP547 Differential Expansion Monitors
are compatible with LVDT and proximity probe inputs, they
provide a 4-20 mA output proportional to the overall measurement.
Each unit provides power for the associated transducer,
processes the signal, and outputs a 4-20 mA dc current that
is proportional to a user specified range such as 0-2 inches.
Combining monitors with an existing PLC or DCS system results
in a high density, low cost vibration monitoring system.
With the alarm feature, the unit functions as a complete
single channel monitor that includes alert and danger alarms,
and output relays.
Buffered Output: A BNC connector mounted on the front
of the unit provides access to the buffered transducer output
signal. This includes both the unfiltered vibration signal,
and the DC bias voltage. Portable test equipment or analyzers
like SKF-CM's MicrologTM can be connected to this output
without disturbing other system outputs.
Fault Detection: On board fault detection circuitry continuously
monitors the transducer for normal operation. If a fault
occurs, the output current is reduced to 2 mA to indicate
the fault to the readout system. A red LED on the front
of the unit is turned on to provide a local indication of
the fault.
Alarms: This monitoring option adds two independent set
points, with LED alarm indicators and output relay contacts
(Alert and Danger). Set points are adjustable via potentiometer,
from 0 to 110% of full scale. Each has an adjustable delay
of 1 to 10 seconds. Relay contacts can be independently
configured by the user for either Normally Open (NO) (Standard)
or Normally Closed (NC) operation. Relays are normally de-energized
and can be configured for latching or non-latching (standard)
operation. Latched alarms may be reset locally or by remote
contact closure. SPST Relay contacts are rated 5 Amps @
30 Vdc or 250 Vac for resistive loads. The Alarm option
also provides set point multiplication of 3X via contact
closure (2X available).
Displays And Assemblies: Various display options, NEMA
and explosion-proof enclosures, and assembled multi-channel
systems are available. Consult your sales representative.
Monitoring Systems
Electrical Specifications: Power: +24 Vdc @ 45 mA max.
(30 mA typical at 2 full scale output). Reverse polarity
and transient protection included. (With the Alarm/Relay
option installed: 75 mA max.)
Buffered Output: BNC Connector
Accuracy: 0.5 % of Full Scale Range.
Output: 4-20 mA proportional to the full scale range.
Maximum Load: 600 Ohms Resistive.
Case: Isolated.
Environmental Specifications:
Operating Temp.: -20oC to +80oC (-4oF to +176oF).
Storage Temp.: -55oC to +125oC (-67oF to +257oF).
Relative Humidity: 0 - 95% Non-Condensing.
Mounting: 32 mm (G style) or 35 mm (T style) DIN Rail.
Ordering Example: To order a standard differential expansion
monitor that accepts input from a 10 mV/mil LVDT, such as
the CMCP-LVDT-51A, with a Full Scale of 0-2.0 inches, specify
Part Number: CMCP547A-02-03.
NOTES:
1.The Full Scale option specified at order entry is used
by the factory for initial calibration. However, several
other ranges can be jumper selected in the field.
2.Transducer and Full Scale options not listed in the above
table are available. Contact your sales representative.