Remote Reset
Description:
The CMCP540A Vibration Displacement Monitors are compatible
with proximity probe inputs, they provide a 4-20 mA output
proportional to the overall measurement. Each unit processes
the vibration signal to determine overall amplitude, and
outputs a 4-20 mA dc current that is proportional to a user
specified range such as 5 mils peak to peak. Combining monitors
with an existing PLC or DCS system results in a high density,
low cost vibration monitoring system. The alarm feature
functions as a complete single channel monitor that includes
alert and danger alarms, and output relays.
Buffered Output:
A BNC connector mounted on the front of the unit provides
access to the buffered transducer output signal. This includes
both the unfiltered vibration signal, and the DC bias voltage.
Portable test equipment or analyzers like SKF-CM's MicrologTM
can be connected to this output without disturbing other
system outputs.
Fault Detection:
On board fault detection circuitry continuously monitors
the transducer for normal operation. If a fault occurs,
the output current is reduced to 2 mA to indicate the fault
to the readout system. A red LED on the front of the unit
is turned on to provide a local indication of the fault.
Filters:
For applications that require monitoring specific frequency
bands, optional high-pass and low-pass filters can be specified.
These filters are modular and can be installed by the factory
or in the field. Each module attenuates out-of-band signals
at a rate of approximately 24 dB/octave. Corner frequencies
from 2 Hz to 20 kHz may be specified. Filter modules may
be cascaded to form higher order filters or to create a
band-pass response. Filtering does not effect the buffered
transducer output.
Alarms:
The CMCP540A Vibration Displacement Monitors have two independent
set points, with LED alarm indicators and output relay contacts
(Alert and Danger). Set points are adjustable via potentiometer,
from 0 to 110% of full scale. Each has an adjustable delay
of 1 to 10 seconds. Relay contacts can be independently
configured by the user for either Normally Open (NO) (Standard)
or Normally Closed (NC) operation. Relays are normally de-energized
and can be configured for latching or non-latching (standard)
operation. Latched alarms may be reset locally or by remote
contact closure. SPST Relay contacts are rated 5 Amps @
30 Vdc or 250 Vac for resistive loads. The monitors also
have set point multiplication of 3X via contact closure
(2X available).
Displays And Assemblies:
Various display options, NEMA and explosion-proof enclosures,
and assembled multi-channel systems are available. Consult
your sales representative.
Electrical Specifications:
Power: +24 Vdc @ 45 mA max. (30 mA typical at 2 full scale
output). Reverse polarity and transient protection included.(With
the Alarm/Relay option installed: 75 mA max.)
Frequency Response (Without optional filters): (-3 dB) 2
Hz to 20 kHz.
Buffered Output: BNC Connector 0-20 kHz.
Accuracy: 0.5 % of Full Scale Range.
Output: 4-20 mA proportional to the full scale range.
Maximum Load: 600 Ohms Resistive.
Case: Isolated.
Environmental Specifications:
Operating Temp.: -20oC to +80oC (-4oF to +176oF).
Storage Temp.: -55oC to +125oC (-67oF to +257oF).
Relative Humidity: 0 - 95% Non-Condensing.
Mounting: 32 mm (G style) or 35 mm (T style) DIN Rail.
Ordering Example:
To order a standard vibration displacement monitor that
accepts input from a 100 mV/mil proximity probe, with a
Full Scale of 5 mils peak to peak, specify Part Number:
CMCP540A-100-01.
NOTES: 1.To order factory installed 4-pole filter modules,
add the appropriate suffix to the basic part number: Example:
adding suffix -L500 specifies a 4-pole low-pass filter with
a corner frequency of 500 Hz (30,000 cpm). Adding suffix
- H40 specifies a 4-pole High-Pass filter with a corner
frequency of 40 Hz (2400 cpm). Up to two filter modules
may be specified. Filter modules can be field installed.
If you are unsure about your filter needs, need higher order
filters or a band-pass response, consult the factory or
your regional sales office for assistance in specifying
the correct option numbers. 2.The Full Scale option specified
at order entry is used by the factory for initial calibration.
However, several other ranges can be jumper selected in
the field. 3.Transducer and Full Scale options not listed
in the above table are available. Contact your sales representative.